tag:blogger.com,1999:blog-14881356429977033292024-03-13T21:31:11.888-05:00TanknologyBlogDiscussion of the petroleum storage tank (UST and AST) regulatory compliance industry, hosted by largest company in the world devoted exclusively to tank compliance.Tanknologyhttp://www.blogger.com/profile/09498408795179981376noreply@blogger.comBlogger279125tag:blogger.com,1999:blog-1488135642997703329.post-1228169111125604492020-12-15T08:00:00.000-06:002020-12-15T08:00:06.619-06:00Tank Trouble Tuesday
A fueling facility in Tanknology's Midwest region requested a TankCam inspection of a 3,000 gallon fiberglass tank to inspect for undesirable conditions or abnormal operating conditions. The tank held midgrade unleaded.
The TankCam inspection showed sludge, sediment, residue and pea gravel on the tank bottom. An area of the tank wall showed peeling while a build-up of residue coated the Tanknologyhttp://www.blogger.com/profile/09498408795179981376noreply@blogger.com0tag:blogger.com,1999:blog-1488135642997703329.post-85486227889475479722020-12-08T08:00:00.000-06:002020-12-08T08:00:00.200-06:00Tank Trouble Tuesday
A fueling facility in Tanknology's Midwest region requested a TankCam inspection of a 4,000 gallon fiberglass tank to inspect for undesirable conditions or abnormal operating conditions. The tank held premium unleaded.
The TankCam inspection showed sections of peeling and flaking on the tank walls. The tank bottom contained sediment, residue and pieces of debris. The inspection also Tanknologyhttp://www.blogger.com/profile/09498408795179981376noreply@blogger.com0tag:blogger.com,1999:blog-1488135642997703329.post-22894041718891408832020-12-01T08:00:00.000-06:002020-12-01T08:00:00.320-06:00Tank Trouble Tuesday
A fueling facility in Tanknology's Midwest region requested a TankCam inspection of a 6,000 gallon fiberglass tank to inspect for undesirable conditions or abnormal operating conditions. The tank held diesel.
The TankCam inspection showed corrosion was on the ball float assembly and an unused bung. The inspection also showed residue on some areas of the lower tank walls. The STP shaft Tanknologyhttp://www.blogger.com/profile/09498408795179981376noreply@blogger.com0tag:blogger.com,1999:blog-1488135642997703329.post-39727129091845034892020-11-24T08:00:00.000-06:002020-11-24T08:00:00.217-06:00Tank Trouble Tuesday
A fueling facility in Tanknology's Midwest region requested a TankCam inspection of a 10,000 gallon fiberglass tank to inspect for undesirable conditions or abnormal operating conditions. The tank held regular unleaded.
The TankCam inspection showed a build-up of residue on the bottom half of the tank. The tank walls exhibited some areas of white streaking and staining and corrosion was Tanknologyhttp://www.blogger.com/profile/09498408795179981376noreply@blogger.com0tag:blogger.com,1999:blog-1488135642997703329.post-82353447416072960992020-11-17T08:00:00.000-06:002020-11-17T08:00:00.235-06:00Tank Trouble Tuesday
A fueling facility in Tanknology's Northeast region requested a TankCam inspection of a 6,000 gallon fiberglass tank to inspect for undesirable conditions or abnormal operating conditions. The tank held diesel.
The TankCam inspection showed sediment and a small amount of residual liquid on the tank bottom .
The inspection also showed that oxidation and corrosion covered the STP shaft.
Tanknologyhttp://www.blogger.com/profile/09498408795179981376noreply@blogger.com0tag:blogger.com,1999:blog-1488135642997703329.post-69674256290680490892020-11-10T08:00:00.000-06:002020-11-10T08:00:00.698-06:00Tank Trouble Tuesday
A fueling facility in Tanknology's Southeast region requested a TankCam inspection of a 8,000 gallon steel tank to inspect for undesirable conditions or abnormal operating conditions. The tank held regular unleaded.
The TankCam inspection showed that the lining of the tank appeared had detached from most of the tank surface. Much of the lining that had detached from the tank surface was Tanknologyhttp://www.blogger.com/profile/09498408795179981376noreply@blogger.com0tag:blogger.com,1999:blog-1488135642997703329.post-4012119343011972942020-11-03T08:00:00.000-06:002020-11-03T08:00:01.112-06:00Tank Trouble Tuesday
A fueling facility in Tanknology's Southeast region requested a TankCam inspection of a 8,000 gallon steel tank to inspect for undesirable conditions or abnormal operating conditions. The tank held regular unleaded.
The TankCam inspection showed that the lining of the tank had detached from most of the tank surfaces. A large sheet of the lining was hanging from a manway. Water was Tanknologyhttp://www.blogger.com/profile/09498408795179981376noreply@blogger.com0tag:blogger.com,1999:blog-1488135642997703329.post-30561983660469900812020-10-27T08:00:00.000-05:002020-10-27T08:00:00.877-05:00Tank Trouble Tuesday
A fueling facility in Tanknology's Midwest region requested a TankCam inspection of a 9,000 gallon fiberglass tank to inspect for undesirable conditions or abnormal operating conditions. The tank held premium unleaded.
The TankCam inspection showed the tank bottom contained sediment and a small amount of residual liquid. Oxidation and corrosion covered the STP shaft.
TankCam® video Tanknologyhttp://www.blogger.com/profile/09498408795179981376noreply@blogger.com0tag:blogger.com,1999:blog-1488135642997703329.post-35500238034423960212020-10-20T08:00:00.000-05:002020-10-20T08:00:04.473-05:00Tank Trouble Tuesday
A fueling facility in Tanknology's Midwest region requested a TankCam inspection of a 15,000 gallon fiberglass tank to inspect for undesirable conditions or abnormal operating conditions. The tank held premium unleaded.
The TankCam inspection showed that the tank bottom contained sediment and a small amount of residual liquid while oxidation and corrosion covered the STP shaft.
Tanknologyhttp://www.blogger.com/profile/09498408795179981376noreply@blogger.com0tag:blogger.com,1999:blog-1488135642997703329.post-43202089923837848542020-10-13T08:00:00.000-05:002020-10-13T08:00:01.067-05:00Tank Trouble Tuesday
A fueling facility in Tanknology's Midwest region requested a TankCam inspection of a 10,000 gallon fiberglass tank to inspect for undesirable conditions or abnormal operating conditions. The tank held premium unleaded.
The TankCam inspection showed sediment and debris on the tank bottom. When vacuum was pulled on the tank, bubbling was observed at one end of the tank. The bubbles Tanknologyhttp://www.blogger.com/profile/09498408795179981376noreply@blogger.com0tag:blogger.com,1999:blog-1488135642997703329.post-58759399113684213212020-10-06T09:00:00.000-05:002020-10-06T09:00:05.065-05:00Tank Trouble Tuesday
A fueling facility in Tanknology's Midwest region requested a TankCam inspection of a 8,000 gallon lined steel tank to inspect for undesirable conditions or abnormal operating conditions. The tank held unleaded.
The TankCam inspection showed no active water ingress during the inspection. The inspection showed many irregular surfaces in the lining material and corrosion in the manway and Tanknologyhttp://www.blogger.com/profile/09498408795179981376noreply@blogger.com0tag:blogger.com,1999:blog-1488135642997703329.post-81025981706703362822020-09-29T08:00:00.000-05:002020-09-29T08:00:02.731-05:00Tank Trouble Tuesday
A fueling facility in Tanknology's Midwest region requested a TankCam inspection of a 4,000 gallon fiberglass tank to inspect for undesirable conditions or abnormal operating conditions. The tank held mid-grade unleaded.
The TankCam inspection showed discoloration throughout the tank. Residue and flaking residue were observed in tank along with sludge and debris. The inspection also Tanknologyhttp://www.blogger.com/profile/09498408795179981376noreply@blogger.com0tag:blogger.com,1999:blog-1488135642997703329.post-73137069285966342462020-09-22T08:00:00.000-05:002020-09-22T08:00:05.591-05:00Tank Trouble Tuesday
A fueling facility in Tanknology's Midwest region requested a TankCam inspection of a 4,000 gallon fiberglass tank to inspect for undesirable conditions or abnormal operating conditions. The tank held diesel.
The TankCam inspection showed an active water ingress near the ATG bung. The inspection also showed a possible crack near the ATG bung and corrosion on the STP shaft. Residue was Tanknologyhttp://www.blogger.com/profile/09498408795179981376noreply@blogger.com0tag:blogger.com,1999:blog-1488135642997703329.post-41827043382592113192020-09-15T08:00:00.000-05:002020-09-15T08:00:00.862-05:00Tank Trouble Tuesday
A fueling facility in Tanknology's Ohio Valley region requested a TankCam inspection of an 8,000 gallon fiberglass tank to inspect for undesirable conditions or abnormal operating conditions. The tank held premium unleaded.
The TankCam inspection showed cracks with an active water ingress along center seam on both sides of tank and possibly, on the bottom of the tank. Several patches Tanknologyhttp://www.blogger.com/profile/09498408795179981376noreply@blogger.com0tag:blogger.com,1999:blog-1488135642997703329.post-65359505834963457442020-09-08T08:00:00.000-05:002020-09-08T08:00:00.620-05:00Tank Trouble Tuesday
A healthcare facility in Tanknology's Midwest region requested a TankCam inspection of a 12,000 gallon fiberglass tank to inspect for undesirable conditions or abnormal operating conditions. The tank held jet A fuel.
The TankCam inspection showed cosmetic blemishes in the tank. The inspection also showed minor residue on the bottom of tank and corrosion in the ATG riser pipe.
Tanknologyhttp://www.blogger.com/profile/09498408795179981376noreply@blogger.com0tag:blogger.com,1999:blog-1488135642997703329.post-48908667140836847842020-09-01T08:00:00.000-05:002020-09-01T08:00:03.691-05:00Tank Trouble Tuesday
A fueling facility in Tanknology's Ohio Valley region requested a TankCam inspection of a 8,000 gallon fiberglass tank to inspect for undesirable conditions or abnormal operating conditions. The tank held regular unleaded.
The TankCam inspection showed residue on the sides of the tank. Flaking and peeling were observed at the riser bungs and along the tank seams. Several ATG Tanknologyhttp://www.blogger.com/profile/09498408795179981376noreply@blogger.com0tag:blogger.com,1999:blog-1488135642997703329.post-56314648237329385712020-08-25T08:00:00.000-05:002020-08-25T08:00:00.273-05:00Tank Trouble Tuesday
A fueling facility in Tanknology's Ohio Valley region requested a TankCam inspection of a 8,000 gallon fiberglass tank to inspect for undesirable conditions or abnormal operating conditions. The tank held regular unleaded.
The TankCam inspection showed streaking at the riser bungs. Several drops per minute of liquid were observed, falling into product from near the STP and fill risers. Tanknologyhttp://www.blogger.com/profile/09498408795179981376noreply@blogger.com0tag:blogger.com,1999:blog-1488135642997703329.post-78441140118993053292020-08-18T08:00:00.000-05:002020-08-18T08:00:03.343-05:00Tank Trouble Tuesday
A fueling facility in Tanknology's Ohio Valley region requested a TankCam inspection of a 8,000 gallon fiberglass tank to inspect for undesirable conditions or abnormal operating conditions. The tank held regular unleaded.
The TankCam inspection showed residue on both sides of the tank. Sludge and sediment were seen on the bottom of tank and flaking and peeling could be found along Tanknologyhttp://www.blogger.com/profile/09498408795179981376noreply@blogger.com0tag:blogger.com,1999:blog-1488135642997703329.post-34388318472034032822020-08-11T08:00:00.000-05:002020-08-11T08:00:00.339-05:00Tank Trouble Tuesday
A fueling facility in Tanknology's Midwest region requested a TankCam inspection of a fiberglass tank to inspect for undesirable conditions or abnormal operating conditions. The customer also requested a TankClean Remote Video UST Cleaning.
The TankCam inspection revealed considerable sludge buildup on the bottom of the tank. After the TankClean Remote Video UST Cleaning, the Tanknologyhttp://www.blogger.com/profile/09498408795179981376noreply@blogger.com0tag:blogger.com,1999:blog-1488135642997703329.post-48090925087999300372020-08-04T08:00:00.000-05:002020-08-04T08:00:03.139-05:00Tank Trouble Tuesday
A fueling facility in Tanknology's Midwest region requested a TankCam inspection of a 15,000 gallon steel tank to inspect for undesirable conditions or abnormal operating conditions. The tank held diesel.
The TankCam inspection revealed corrosion and pitting throughout tank. The bottom of tank was obscured by sludge and product. A water ingress was found on the side of the tank and other Tanknologyhttp://www.blogger.com/profile/09498408795179981376noreply@blogger.com0tag:blogger.com,1999:blog-1488135642997703329.post-43557439923744981312020-07-28T08:00:00.000-05:002020-07-28T08:00:07.084-05:00Tank Trouble Tuesday
A fueling facility in Tanknology's Ohio Valley region requested a TankCam inspection of a 10,000 gallon fiberglass tank to inspect for undesirable conditions or abnormal operating conditions. The tank held premium unleaded.
The TankCam inspection revealed corrosion on the ball valve riser. Multiple layers of liquid were seen in the bottom of tank and an unknown liquid was observed seepingTanknologyhttp://www.blogger.com/profile/09498408795179981376noreply@blogger.com0tag:blogger.com,1999:blog-1488135642997703329.post-45902631101857750962020-07-21T08:00:00.000-05:002020-07-21T08:00:08.760-05:00Tank Trouble Tuesday
A fueling facility in Tanknology's Ohio Valley region requested a TankCam inspection of a 4,000 gallon fiberglass tank to inspect for undesirable conditions or abnormal operating conditions. The tank held kerosene.
The TankCam inspection revealed that the metallic components of the tank exhibited light corrosion while showing that the tank bottom contained sediment and debris.
Tanknologyhttp://www.blogger.com/profile/09498408795179981376noreply@blogger.com0tag:blogger.com,1999:blog-1488135642997703329.post-42715068771422260322020-07-14T08:00:00.000-05:002020-07-14T08:00:08.067-05:00Tank Trouble Tuesday
A fueling facility in Tanknology's Southeast region requested a TankCam® inspection of a 10,000 gallon doublewalled fiberglass tank to inspect for undesirable conditions or abnormal operating conditions. The tank held premium unleaded.
The TankCam inspection revealed minor water ingress along a tank seam. The inspection also showed debris on the bottom of the tank including gaskets and Tanknologyhttp://www.blogger.com/profile/09498408795179981376noreply@blogger.com0tag:blogger.com,1999:blog-1488135642997703329.post-53144180181074236222020-07-07T08:00:00.000-05:002020-07-07T08:00:08.001-05:00Tank Trouble Tuesday
A fueling facility in Tanknology's Ohio Valley region requested a TankCam® inspection of a 10,000 gallon fiberglass tank to inspect for undesirable conditions or abnormal operating conditions. The tank held regular unleaded.
The TankCam inspection showed residue, sediment and debris on the tank bottom. A suspicious area near and endcap, resembling a possible crack, was also observedTanknologyhttp://www.blogger.com/profile/09498408795179981376noreply@blogger.com0tag:blogger.com,1999:blog-1488135642997703329.post-56984095522082153682020-06-30T08:00:00.000-05:002020-06-30T08:00:15.899-05:00Tank Trouble Tuesday
A fueling facility in Tanknology's Ohio Valley region requested a TankCam® inspection of a 10,000 gallon fiberglass tank to inspect for undesirable conditions or abnormal operating conditions. The tank held regular unleaded.
The TankCam inspection revealed residue, sediment, and debris on the lower half of the tank. The inspection also showed areas of exposed fibers and a drip Tanknologyhttp://www.blogger.com/profile/09498408795179981376noreply@blogger.com0